Harmonic Filters
MTE offers an array of harmonic mitigation solutions, including the best THID reduction solution on the market with patented Adaptive Passive Technology, to increase productivity and system efficiency.
Matrix® AP Performance Guarantee
Matrix filters can also provide similar performance in other drive applications such as constant torque, DC drives and other phase controlled rectifiers, but actual THID levels can vary by load and/or speed and therefore cannot be guaranteed. Consult factory for assistance when applying Matrix filters on these types of equipment.
MINIMUM SYSTEM REQUIREMENTS
The guaranteed performance levels of this filter will be achieved when the following system conditions are met:
Frequency: | Nominal Frequency ± 0.75Hz |
System Voltage: | Nominal System Voltage (line to line) ±10% |
Balanced Line Voltage: | Within 1% |
Background Voltage Distortion: | 0% THVD |
NOTE: The presence of background voltage distortion will cause motors and other linear loads to draw harmonic currents. Additional harmonic currents may flow into the Matrix filter if there is harmonic voltage distortion already on the system.
Downloadable PDF Version
Matrix AP Performance Guarantee